..
Pump station [1 - 4]
Type
Designation
Pumps: Count
Pumps: Change-over: Type
Pumps: Change-over: Time
Dependency: Burner
External release 1
External release 2
Dependency: Operation modes
Boost
Control valve: Control value
Level: Actual value
Start: Level: Less than or equal to
Stop: Level: Greater or equal
Start: Delay
Stop: Delay
Pumps: External: Start
Handling
Pump 1
Pump 2
Pumps: Change-over: Automatic according to operating duration
Pressure: Switch: MIN
Parameter
Description
Level above which the pump is stopped (e.g. water level 350 mm).
Properties
Floating point
Level of actual value Y0
Level of actual value Y1
Level of actual value unit
Reference
6548; 6549; 6550; 6551
DOC-723125867