Pump station [1 - 4]
Type
Designation
Pumps: Count
Pumps: Change-over: Type
Pumps: Change-over: Time
Dependency: Burner
External release 1
External release 2
Dependency: Operation modes
Boost
Control valve: Control value
Level: Actual value
Start: Level: Less than or equal to
Stop: Level: Greater or equal
Start: Delay
Stop: Delay
Pumps: External: Start
Handling
Pump 1
Pump 2
Pumps: Change-over: Automatic according to operating duration
Pressure: Switch: MIN
Parameter
Description
If the type of the pump control system requires a level...
Pump station [1 - 4]: Type = setting value of control valve > 1%
Pump station [1 - 4]: Type = level control: 2 point control
...then the level (e.g. boiler water level) must be read in via an analog channel. The value is shown on the HMI and used for the operation release.
Properties
Selection analog input channel
Reference
4333; 4334; 4335; 4336