Pump station [1 - 4]: Dependency: Burner

Parameter

Description

In addition to the release contacts and the type of pump control system, a dependency to the burner or to combustion can be created. This influences when the pump(s) is/are started. This is always the starting time. The release generally ceases if the FSC no longer requests the combustion air fan. Consequently, post-purging and the fan run-on are always part of the control release.

Properties

Type

Selection parameter

[0] No dependency
[1] From time burner selected
[2] From time burner requested
[3] From time purge position reached
[4] From time ignition position requested
[5] From time ignition position reached
[6] From time start ignition
[7] From time burner in operation

Reference

4289; 4290; 4291; 4292

DOC-720965095