Pump station [1 - 4]: Pumps: Change-over: Time

Parameter

Description

This parameter is dependent on Pump station [1 - 4]: Pumps: Change-over: Type

Function of this parameter depending on the pump switching:

[0]

Delay time until pump B is started after pump A is no longer requested.

[1]

Delay time until pump B is started after pump A is no longer requested.

[2]

The duration of the operation overlap of both pumps until pump A is stopped (pump B is the primary pump).

Properties

Type

Integer

Min

0

Max

3600

Unit

s

Reference

4056; 4057; 4058; 4059

DOC-720965083