Pump station [1 - 4]: Pumps: Change-over: Type

Parameter

Description

Defines the type of switching between two pumps.

Properties

Type

Selection parameter

[0] Only if no pump is operating.

Pump A must be switched off before changing over to Pump B. The pump does not switch off automatically.

[1] Automatic switchover without simultaneous operation

Pump A is automatically switched off. Then Pump B is started with a configurable delay.

[2] Automatic switchover with smooth transition

In the case of this pump switchover, an overlap occurs in which Pump A <emphasis role="bold">and</emphasis> Pump B are requested by the system and both operational feedback messages must be present.

Reference

4060; 4061; 4062; 4063